Quality 16 Unit R290 Cascade Heat Pumps Serve 75C Radiator Systems In Hotels factory
Quality 16 Unit R290 Cascade Heat Pumps Serve 75C Radiator Systems In Hotels factory

16 Unit R290 Cascade Heat Pumps Serve 75C Radiator Systems In Hotels

16 Unit R290 Cascade Heat Pumps Serve 75C Radiator Systems In Hotels
Basic Properties
Country Of Origin
China
Brand Name
ZOVIV
Certificate
Available
PRODUCT MODEL
PW30-DKXLRE3-H8
Trading Properties
MOQ
3 pcs
Unit Price
$7500-13000
Payment Method
L/C,D/A,D/P,T/T
Supply Capacity
200pcs 30days
Product Summary

Industrial R290 cascade heat pumps deliver 75°C flow for direct boiler retrofits, operating down to -25°C with A+++ efficiency. Up to 16-unit cascade ensures redundancy, while §14a EnWG compliance, SG/PV-ready control, and two-level leak protection cut OPEX and ensure safety.

Product Details
Highlight:

75C R290 Cascade Heat Pumps

,

Hotel R290 Cascade Heat Pumps

,

16 Unit Cascade Heat Pump

Power Supply: 380-415V, 3N~, 50/60Hz
Type: Air Source Heat Pump
Operating Ambient Temp.: -25~43°C
Refrigerant: R290
App-Controlled: Yes
Net Weight: 260kg
Max. Power Input: 17kW
Water Pressure Drop (Max): 55kPa
Product Description
Commercial R290 Full DC Inverter Monoblock Heat Pump Series

The Commercial R290 Full DC Inverter Monoblock Heat Pump Series is an industrial-grade hydronic climate engine engineered for large-scale space heating, space cooling, and high-temperature hot water generation. Built to deliver uninterrupted thermal output in cold-climate environments down to -25°C, the system replaces fossil-fuel boilers and traditional chillers in commercial buildings, hotels, hospitals, and residential complexes. Featuring a scalable 16-unit cascade architecture, 75°C flow temperature output, and a two-level refrigerant leakage protection protocol, it offers a future-proof, low-OPEX HVAC solution for modern enterprise infrastructure.

Technical Differentiation & Engineering Breakthroughs
Scalable 16-Unit Cascade Logic for Zero-Downtime Operations

Single large central chillers represent a critical single-point-of-failure risk and incur severe partial-load efficiency losses. This series supports central master-slave networking for up to 16 individual units. The integrated system controller dynamically balances running hours across compressors and modulates system capacity in response to real-time building thermal demand, ensuring continuous operational redundancy and optimal partial-load COP.

German EnWG Section 14a Grid Compliance & SG/PV Synergy

Designed for seamless integration into European smart grid infrastructure, the unit natively complies with German §14a EnWG regulations for active grid load management. Combined with SG-Ready and PV-Ready hardware protocols, the control architecture automatically shifts heat production to periods of excess solar generation or off-peak electricity rates, drastically reducing annual utility expenses for commercial property managers.

Enterprise Hydrocarbon Safety Architecture

Deploying low-GWP natural R290 refrigerant (GWP = 3) in high-capacity commercial installations requires robust safety engineering. The series utilizes a two-level active leakage mitigation design. Continuous monitoring sensors detect micro-concentrations of gas within the sealed outdoor cabinet, instantly activating automatic circuit isolation and forced exhaust ventilation procedures to maintain complete facility safety.

75°C Hydronic Output for Accelerated Boiler Retrofits

Modernizing legacy commercial hydronic systems often faces structural constraints when existing radiators cannot be replaced. Delivering supply water up to 75°C without supplementary electric heating elements, this series allows direct drop-in replacement of gas or oil boilers while utilizing the building's existing high-temperature hydronic distribution network.

Technical Specifications
  • Equipment Classification: Heavy-Duty Commercial Air-to-Water Heat Pump
  • Operating Modes: Space Heating, Space Cooling, High-Temperature Hot Water
  • Refrigerant Medium: Low-GWP Natural R290 (GWP = 3)
  • Safety Rating: Integrated Two-Level Active Refrigerant Leakage Protection
  • Seasonal Energy Class: ERP A+++ (at 35°C and 55°C Flow Temperatures)
  • Maximum Water Outlet Temperature: 75°C
  • Operating Ambient Temperature Limit: Fully Functional Down to -25°C
  • Hydronic Freeze Defense: Integrated Mechanical Antifreeze Drain Valve
  • Multi-Unit Capacity Scaling: Up to 16 Units Centralized Cascade Control
  • Operational Acoustic Output: Low Sound Pressure Down to 45 dB(A) at 1 Meter
  • System Management Interface: 7-Inch Color Touchscreen with Smart Life WiFi & IoT Cloud
  • Energy Protocol Support: German §14a EnWG Compliant, SG-Ready, PV-Ready Terminals
Commercial Value for MEP Contractors & Facility Developers
  • Reduced On-Site Labor: Factory-sealed monobloc housing retains all refrigerant handling outdoors, eliminating the need for specialized F-gas pipe brazing inside the building.
  • Optimized Government Subsidies: ERP A+++ seasonal energy efficiency, zero-ODP natural refrigerant profile, and §14a EnWG grid compliance satisfy core requirements for European commercial clean-energy equipment grants.
  • Low Acoustic Footprint: Operating at sound levels as low as 45 dB(A) at 1 meter allows direct installation in acoustic-sensitive commercial zones near residential property boundaries.
16 Unit R290 Cascade Heat Pumps Serve 75C Radiator Systems In Hotels
Parameter / Feature PW20-DKXLRE3-H8 PW30-DKXLRE3-H8
Heating Condition - Ambient Temp.(DB/WB): 7/6°C, Water Temp.(In/Out): 30/35°C
Nominal Capacity (kW) 20.0 30.0
Nominal Power Input (kW) 4.30 6.52
COP 4.65 4.60
Heating Condition - Ambient Temp.(DB/WB): 7/6°C, Water Temp.(In/Out): 47/55°C
Nominal Capacity (kW) 20.0 30.0
Nominal Power Input (kW) 7.14 10.91
COP 2.8 2.75
Cooling Condition - Ambient Temp.(DB/WB): 35/24°C, Water Temp.(In/Out): 23/18°C
Nominal Capacity (kW) 20.0 30.0
Nominal Power Input (kW) 4.35 6.55
EER 4.60 4.58
Operating Ranges & Capacity Ratings
Heating Capacity Range (kW) 11.2~28.0 14.0~40.0
Heating Power Input Range (kW) 2.23~7.67 2.83~11.08
COP Range 3.65~5.02 3.61~4.95
DHW Condition - Ambient Temp.(DB/WB): 20/15°C, Water Temp.(In/Out): 15/55°C
Heating Capacity Range (kW) 11.8~29.0 16.0~42.0
Heating Power Input Range (kW) 2.34~7.53 3.21~11.05
COP Range 3.85~5.04 3.80~4.98
Heated Water Output (L/H) 624 903
Cooling Condition - Ambient Temp.(DB/WB): 35/24°C, Water Temp.(In/Out): 12/7°C
Cooling Capacity Range (kW) 8.2~21.0 11.5~30.0
Cooling Power Input Range (kW) 2.55~7.92 3.59~11.54
EER Range 2.65~3.21 2.60~3.20
Cooling Condition - Ambient Temp.(DB/WB): 35/24°C, Water Temp.(In/Out): 23/18°C (Range)
Cooling Capacity Range (kW) 10.5~25.5 12.6~33.5
Cooling Power Input Range (kW) 2.08~6.66 2.52~8.82
EER Range 3.83~5.05 3.80~5.00
Energy Efficiency Ratings (ErP)
ErP Level (55°C) A+++ A+++
ErP Level (35°C) A+++ A+++
Electrical & Hydraulic Specifications
Power Supply 380-415V, 3N~, 50/60Hz 380-415V, 3N~, 50/60Hz
Max. Power Input (kW) 12 17
Max. Current (A) 22.8 34.2
Fuse or Circuit Breaker (A) 32 40
Wire Diameter mm² 6mm² 6mm²
Diameter of Pipe (mm) DN40 DN40
Water Flow (m³/h) 4.82 6.88
Water Pressure Drop (max) kPa 55 60
Physical & Operating Specifications
Net Weight (kg) 230 260
Body Size (W*D*H) (mm) 1375×532×1565 1550×630×1708
IP Grade (Level of Protection) IPX4 IPX4
Refrigerant R290 R290
Operating Ambient Temp. (°C) -25~43°C -25~43°C
Operating Water Temp. (°C) 25~75°C (DHW)
25~75°C (Heating)
5~30°C (Cooling)
25~75°C (DHW)
25~75°C (Heating)
5~30°C (Cooling)
Note: The data above is for reference only, please refer to the nameplate on the unit for more specific data.