R290 Commercial Air Source Heat Pump with 16 Unit Cascade and 75°C Output for Central Heating
R290 commercial air source heat pump with 16-unit cascade control, 75°C high-temperature output and reliable -25°C heating for large central HVAC projects.
Inverter R290 Heat Pump
,Cascade R290 Heat Pump
,Commercial R290 Heat Pump
The R290 Commercial Full DC Inverter Air Source Heat Pump Series is an industrial-grade hydronic climate system engineered for large-scale space heating, comfort cooling, and high-temperature hot water generation. Operating on eco-friendly natural R290 refrigerant (GWP = 3) and powered by full DC inverter modulation, this heavy-duty unit delivers reliable thermal performance in severe winter conditions down to -25°C.
Designed specifically for scalable commercial HVAC installations, the system supports multi-unit cascade setups of up to 16 units, producing outlet water temperatures up to 75°C to replace central gas boilers and chilling plant infrastructure in commercial facilities, apartment complexes, and institutional buildings.
Unlike traditional rigid central chillers that require massive plant room footprints and single-point-of-failure reliance, this commercial series features an intelligent multi-unit cascade control protocol. Up to 16 individual heat pumps can be networked together under centralized master-slave management. The system controller automatically stages capacity up or down to match dynamic building heat loads, ensuring continuous operational redundancy and optimizing partial-load efficiency across large commercial square footage.
Deploying hydrocarbon refrigerants in high-capacity commercial projects demands rigorous safety engineering. The series is built with a two-level active safety protection architecture. Specialized sensors constantly scan internal cabinet compartments for micro-leaks, automatically triggering localized electrical isolation and forced ventilation sequences to preserve complete system safety during heavy operational cycles.
Commercial outdoor installations exposed to extreme sub-zero weather risk catastrophic frost damage during power interruptions or low-flow standby modes. The unit incorporates a mechanical precision antifreeze drain valve coupled with intelligent automated circulating routines, providing fail-safe protection against internal heat exchanger freezing in cold-climate regions down to -25°C.
To minimize peak demand utility charges for building operators, the heat pump features native SG-Ready (Smart Grid) logic and PV-ready hardware inputs. The central system controller automatically prioritizes low-cost off-peak grid power or surplus electricity generated from rooftop photovoltaic arrays, storing thermal energy in hydronic buffer tanks to drastically cut commercial electricity bills.
- Equipment ClassificationHeavy-Duty Commercial Air-to-Water Heat Pump
- Operating ModesLarge-Scale Space Heating, Space Cooling, High-Temp Hot Water
- Refrigerant MediumLow-GWP Natural R290 (GWP = 3)
- Safety RatingSpecialized Two-Level Refrigerant Leakage Protection
- Maximum Water Supply Temperature75°C
- Low Ambient Operational RangeFully Functional Down to -25°C
- Seasonal Energy Efficiency ClassERP A+++ (at 35°C and 55°C Flow Temperatures)
- Multi-Unit Network CapacityUp to 16 Units Integrated Cascade Management
- Acoustic Pressure OutputLow Noise Design Down to 45 dB(A) at 1 Meter
- Hydronic Freeze MitigationMechanical Precision Antifreeze Drain Valve Integration
- System Management7-Inch Touchscreen Controller with Smart App WiFi and IoT Cloud
- Grid and Renewable IntegrationNative SG-Ready Logic, PV-Ready Terminals
- High Operational Redundancy: Multi-unit cascade logic ensures building climate control remains active even if a single unit undergoes routine maintenance.
- Simplified Field Plumbing: Factory-sealed monobloc units keep all refrigerant handling outdoor, removing the requirement for specialized on-site F-gas pipe brazing.
- Optimized Commercial Subsidies: ERP A+++ energy certification, zero-ODP natural refrigerant profile, and smart grid compatibility meet key criteria for European clean-energy commercial equipment grants.
| Parameter / Feature | PW20-DKXLRE3-H8 | PW30-DKXLRE3-H8 |
|---|---|---|
| Heating Condition — Ambient Temp. (DB/WB): 7/6°C, Water Temp. (In/Out): 30/35°C | ||
| Nominal Capacity (kW) | 20.0 | 30.0 |
| Nominal Power Input (kW) | 4.30 | 6.52 |
| COP | 4.65 | 4.60 |
| Heating Condition — Ambient Temp. (DB/WB): 7/6°C, Water Temp. (In/Out): 47/55°C | ||
| Nominal Capacity (kW) | 20.0 | 30.0 |
| Nominal Power Input (kW) | 7.14 | 10.91 |
| COP | 2.8 | 2.75 |
| Cooling Condition — Ambient Temp. (DB/WB): 35/24°C, Water Temp. (In/Out): 23/18°C | ||
| Nominal Capacity (kW) | 20.0 | 30.0 |
| Nominal Power Input (kW) | 4.35 | 6.55 |
| EER | 4.60 | 4.58 |
| Operating Ranges & Capacity Ratings | ||
| Heating Capacity Range (kW) | 11.2~28.0 | 14.0~40.0 |
| Heating Power Input Range (kW) | 2.23~7.67 | 2.83~11.08 |
| COP Range | 3.65~5.02 | 3.61~4.95 |
| DHW Condition — Ambient Temp. (DB/WB): 20/15°C, Water Temp. (In/Out): 15/55°C | ||
| Heating Capacity Range (kW) | 11.8~29.0 | 16.0~42.0 |
| Heating Power Input Range (kW) | 2.34~7.53 | 3.21~11.05 |
| COP Range | 3.85~5.04 | 3.80~4.98 |
| Heated Water Output (L/H) | 624 | 903 |
| Cooling Condition — Ambient Temp. (DB/WB): 35/24°C, Water Temp. (In/Out): 12/7°C | ||
| Cooling Capacity Range (kW) | 8.2~21.0 | 11.5~30.0 |
| Cooling Power Input Range (kW) | 2.55~7.92 | 3.59~11.54 |
| EER Range | 2.65~3.21 | 2.60~3.20 |
| Cooling Condition — Ambient Temp. (DB/WB): 35/24°C, Water Temp. (In/Out): 23/18°C (Range) | ||
| Cooling Capacity Range (kW) | 10.5~25.5 | 12.6~33.5 |
| Cooling Power Input Range (kW) | 2.08~6.66 | 2.52~8.82 |
| EER Range | 3.83~5.05 | 3.80~5.00 |
| Energy Efficiency Ratings (ErP) | ||
| ErP Level (55°C) | A+++ | A+++ |
| ErP Level (35°C) | A+++ | A+++ |
| Electrical & Hydraulic Specifications | ||
| Power Supply | 380-415V, 3N~, 50/60Hz | 380-415V, 3N~, 50/60Hz |
| Max. Power Input (kW) | 12 | 17 |
| Max. Current (A) | 22.8 | 34.2 |
| Fuse or Circuit Breaker (A) | 32 | 40 |
| Wire Diameter (mm²) | 6mm² | 6mm² |
| Diameter of Pipe (mm) | DN40 | DN40 |
| Water Flow (m³/h) | 4.82 | 6.88 |
| Water Pressure Drop (max) kPa | 55 | 60 |
| Physical & Operating Specifications | ||
| Net Weight (kg) | 230 | 260 |
| Body Size (W×D×H) (mm) | 1375×532×1565 | 1550×630×1708 |
| IP Grade (Level of Protection) | IPX4 | IPX4 |
| Refrigerant | R290 | R290 |
| Operating Ambient Temp. (°C) | -25~43°C | -25~43°C |
| Operating Water Temp. (°C) | 25~75°C (DHW) 25~75°C (Heating) 5~30°C (Cooling) |
25~75°C (DHW) 25~75°C (Heating) 5~30°C (Cooling) |
Note: The data above is for reference only. Please refer to the nameplate on the unit for more specific data.